Permit: T19CM04120

Parcel: 103082620

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/23/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Not ready for inspection
08/23/2019 PLUMBING - INTERMEDIATE Approved Based on photos supplied by the contractor
08/22/2019 PLUMBING - INTERMEDIATE Denied 1- Reference comments from previous inspection.
08/21/2019 PLUMBING - INTERMEDIATE Denied 1- Shall locate the horizontal vent for the second floor water closet a minimum of 6 inches above the flood level rim of the fixture.
2- Shall provide a clean out on the 2 inch waste stack.
3- Shall secure the horizontal water lines every 32 inches.
4- Shall extend the vent for the second floor lavatories thru the roof.
08/16/2019 PLUMBING - INTERMEDIATE Denied 1- Plumbing is incomplete inspection stop.