Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
Clear electric INCR , DGC |
| 08/20/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
existing ground is not sufficient nor does it appear that’s its even tied into the new panel. Please provide two ground rods 6 foot apart and bond water and gas. Panel needs address label and breakers need to be labeled. |