Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
Clear incr |
| 06/07/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
this is not an increase just a panel relocation. Panel needs proper grounding two ground rods 6 foot apart. Bond gas and water. Panel needs address label. Panel missing dead front. Incorrect conduit to current panel will need to be addressed before final. |