Permit: T19CM03948

Parcel: 125070790


Addresses:

2548 E 4TH ST

Inspection Status: Approved

Inspection History: RESIDENTIAL INTERMEDIATE

Date Description Inspector Results Comments
07/29/2019 RESIDENTIAL INTERMEDIATE Approved
07/24/2019 RESIDENTIAL INTERMEDIATE Partial Approval Electrical: CO
Halo can in shower required GFCI protection per manufacturer.
Brick wall left of pass door, NM installed requires metal protection from screws or nails.

Plumbing: CO
Secure shower nozzle outlet so it is firmly attached for all future use.
Lavies/sinks. Two traps not allowed on one dirty arm. Fix discussed with Contractor.
Vents horizontal, shall be 6” higher than the flood rim of the bowl they serve.
Toilet closet ring shall be firmly screwed to the floor using all holes provided.

Mechanical: AP
Existing floor register.