Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2019 | RESIDENTIAL INTERMEDIATE | Approved | ||
| 07/24/2019 | RESIDENTIAL INTERMEDIATE | Partial Approval | Electrical: CO Halo can in shower required GFCI protection per manufacturer. Brick wall left of pass door, NM installed requires metal protection from screws or nails. Plumbing: CO Secure shower nozzle outlet so it is firmly attached for all future use. Lavies/sinks. Two traps not allowed on one dirty arm. Fix discussed with Contractor. Vents horizontal, shall be 6” higher than the flood rim of the bowl they serve. Toilet closet ring shall be firmly screwed to the floor using all holes provided. Mechanical: AP Existing floor register. |