Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2019 | ELECTRIC - SERVICE UPGRADE | Approved | Clear incr | |
| 08/06/2019 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | called 30 minutes ahead per message. No one on site upon arrival and no one answered the door, gates closed. Called that 1:38 PM arrived at 2:09 PM. Waited an additional 10 to 15 minutes due to contractor telling me they were one minute away. Finally left house at 2:22pm as no contractor ever showed up. | |
| 06/13/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | Label all breakers on the dead front panel not on breaker knockouts. Need to see gas bond and water bond Service mast must be supported on two places. TEP may require roof bracing. |