Inspection History Details
Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Final
Permit Number - T19CM03834
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2022 | COT - LCEL - Electrical Final | Canceled | Inspection Canceled | |
10/22/2019 | COT - LCEL - Electrical Final | MRAMBER | Denied | Entered by KROBLES1 - denied. Unable to approve inspection as busbars and electrical panel are burnt beyond repair, electrical panel needs to be replaced, addressed problem with homeowner, instructed homeowner to replace panel, I have expressed the severity of the issue, homeowner acknowledges and stated that he would affect repairs as soon as possible. |
10/16/2019 | COT - LCEL - Electrical Final | BSTEVENS | Partial Approval | Entered by BSTEVENS - (RVI) ALL ELECTRICAL REPAIRS ARE APPROVED, BUT HOLE IN PARAPET WALL NEEDS TO BE PATCHED AND WATERPROOFED PRIOR TO FINAL APPROVAL. |
07/29/2019 | COT - LCEL - Electrical Final | DMUNIZ | Denied | Entered by DMERANZ1 - Work incomplete and is unsafe. Need a licensed Electrician to address multiple issues. Provide Myers HUB for top of Service Entrance. Provide proper conduit and fittings for Electrical run, Need proper connection from conduit to sub panel. Properly strap Vertical conduit and Conduit on the roof, Provide ladder for further inspection. |