Permit: T19CM03834

Parcel: 13615380A

Inspection Status: Canceled

Inspection History: COT - LCEL - Electrical Final 

Permit Number - T19CM03834

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Canceled

Date Description Inspector Results Comments
11/07/2022 COT - LCEL - Electrical Final  Canceled Inspection Canceled
10/22/2019 COT - LCEL - Electrical Final  MRAMBER Denied Entered by KROBLES1 - denied. Unable to approve inspection as busbars and electrical panel are burnt beyond repair, electrical panel needs to be replaced, addressed problem with homeowner, instructed homeowner to replace panel, I have expressed the severity of the issue, homeowner acknowledges and stated that he would affect repairs as soon as possible.
10/16/2019 COT - LCEL - Electrical Final  BSTEVENS Partial Approval Entered by BSTEVENS - (RVI) ALL ELECTRICAL REPAIRS ARE APPROVED, BUT HOLE IN PARAPET WALL NEEDS TO BE PATCHED AND WATERPROOFED PRIOR TO FINAL APPROVAL.
07/29/2019 COT - LCEL - Electrical Final  DMUNIZ Denied Entered by DMERANZ1 - Work incomplete and is unsafe. Need a licensed Electrician to address multiple issues. Provide Myers HUB for top of Service Entrance. Provide proper conduit and fittings for Electrical run, Need proper connection from conduit to sub panel. Properly strap Vertical conduit and Conduit on the roof, Provide ladder for further inspection.