Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
Permit Number - T19CM03771
Inspection Description - PLUMBING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2020 | PLUMBING - FINAL | Partial Approval | REVIEW OF WATER DISINFECTION REPORT COMPLETED | |
03/05/2020 | PLUMBING - FINAL | Approved | ||
02/24/2020 | PLUMBING - FINAL | Not ready for Inspection | Complete all inspections. Provide chlorination report. Provide air balance report. ADA restrooms are non-compliant. Provide concrete stoops minimum 3 ft by 3 foot at exits. Handrails not properly attached at Corredor. | |
09/06/2019 | PLUMBING - FINAL | Prior to Final Inspectn | WATER DISINFECTION REPORT REQUIRED |