Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T19CM03632
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2020 | ELECTRIC - FINAL | Approved | Approved | |
08/07/2019 | ELECTRIC - FINAL | Denied | 1. Label panel for non metallic plumbing and PT slab 2. Outlets at AC unit, back patio, and front entry are not GFCI protected 3. Outlets in bathrooms and kitchen are GFCI but there are not resets installed in the house. The reset is in the panel at the arc fault breaker Note: This home is currently running off generator for power, no meter has been set at this time |