Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2019 | MECHANICAL - FINAL | Approved | ||
| 10/21/2019 | MECHANICAL - FINAL | Not ready for Inspection | Not complete. | |
| 08/30/2019 | MECHANICAL - FINAL | Partial Approval | On access to air handler in attic. Disconnent or lock out missing on water heater. Breaker on condenser is is to high, max 35 amp. Rear hose bib missing anti siphon. |