Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2019 | ELECTRIC - INTERMEDIATE | Approved | ||
| 07/02/2019 | ELECTRIC - INTERMEDIATE | Correction Required | See June 26th comments. | |
| 06/26/2019 | ELECTRIC - INTERMEDIATE | Correction Required | 1-Insulation has been installed; remove to allow inspection. 2-Insta-hot water heater with double 40 amp feeds has been roughed in; plans do not show electric water heater in sub-panel schedule, which is shown as 60 amp. Revise plans to include electrical calculations for as built condition, to determine the minimum size for the sub-panel. |