Permit: T19CM03482

Parcel: 114600830

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T19CM03482

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2020 FIRE - FINAL Approved
03/12/2020 FIRE - FINAL Denied -Modification to the sprinkler system is required.
-Missing sprinkler coverage in back area where new ceilings were installed.
-Pendant sprinklers below uprights in the front need to be removed.
A separate permit for sprinklers is required through the Tucson Fire Department
-Provide and mount 1 fire extinguisher, minimum size 2A-10BC
-Post suite number on the exterior of rear door.
-If this is a state licensed facility an operational permit is required through TFD, an application was left on site.