Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2020 | FIRE - FINAL | Approved | ||
| 03/12/2020 | FIRE - FINAL | Denied | -Modification to the sprinkler system is required. -Missing sprinkler coverage in back area where new ceilings were installed. -Pendant sprinklers below uprights in the front need to be removed. A separate permit for sprinklers is required through the Tucson Fire Department -Provide and mount 1 fire extinguisher, minimum size 2A-10BC -Post suite number on the exterior of rear door. -If this is a state licensed facility an operational permit is required through TFD, an application was left on site. |