Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2019 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 07/03/2019 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
Customer wanted electrical clearance, however access was not available to the suite nor the electrical room. |