Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T19CM03440
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/24/2019 | ELECTRIC - SERVICE UPGRADE | Approved | Inspection for Installation of Electrical Raceway and Conductors from Existing 277/480V, 600 AMP SES Breaker in Electrical room to New Chiller RTU #2. 2 sets Of #350 KCMIL, 2- #1 GRND. Verbal Clearance sent to TEP @ 11:00AM (RECN). |