Permit: T19CM03327

Parcel: 137055380

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/28/2020 FIRE - FINAL Approved
11/15/2019 FIRE - FINAL Partial Approval EM lighting for 1 & 2 now working.
11/14/2019 FIRE - FINAL Partial Approval Revoked TCO for theatres #1 & 2. EM lighting not working.
11/14/2019 FIRE - FINAL Partial Approval Allowed theatres 1 & 2 to remain open under TCO with the following stipulation:
Six employees with flashlights to be stationed inside each theatre while occupied. They are to be stationed at each exit and along the path of egress.
11/13/2019 FIRE - FINAL Partial Approval -Approved to obtain TCO for phase 1.
10/30/2019 FIRE - FINAL Partial Approval -Approved to obtain TCO for lobby/bar.
-Reinspection fee added for partial inspection.