Permit: T19CM03327

Parcel: 137055380

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T19CM03327

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2019 ELECTRIC - INTERMEDIATE Approved
10/10/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- This Inspection is for Theater 1 only.
09/26/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- MC cables and metal boxes are okay in the Service Bar pony wall.
09/18/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- Transformers, two Service Panels and boxes located on the mezzanine level are okay.
2- Electric boxes and MC cables in the Promenade are okay to cover.
09/12/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- Electric MC cable and metal boxes located in the new concession bar and Theater 9 upper level Vomitory is okay to cover.
09/06/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- Steel reinforcement provided in Theater 1
2- Underground electric conduits are okay to cover.
09/04/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- Underground electric conduits in Theater 8 are okay to cover.
2- Metal boxes and MC cables in the bar area and in corridor wall at Theater 3,4,5,6 & 7 are okay for sheet rock.
08/28/2019 ELECTRIC - INTERMEDIATE Partial Approval theaters 5, 6, 7 ok
08/26/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- Steel reinforcement is okay in Theater #5 only.
2- Under slab electric conduits okay.Theater #5 only.
08/22/2019 ELECTRIC - INTERMEDIATE Partial Approval theater 2, 3 ,4 ok
08/19/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- underground electric conduits are okay in Theater #2