Permit: T19CM03226

Parcel: 132130750


Addresses:

3300 S PARK AV

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
02/23/2021 EXCAVATION/LAYOUT REBAR & ZON Approved
11/20/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval Grid line A-B.5/1-7 concrete infill.

Ok to pour
11/05/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval Perimeter of building.
10/25/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval 1- Steel reinforcement okay in footing pads located at grid line K and between grid lines 3.3 and 3.5 and between grid lines 4 & 5 and Elevator pit.
10/24/2019 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection 1- Contractor called and cancelled the inspection request.
10/22/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval Excavation. Partial. Remainder of line A.
10/21/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval 1- Column footings steel reinforcement is okay between grid lines B.5 and 5.5 only.
10/07/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval Gl -m, m1 , m6, m7.1
Gl - k, f6 12 7 off of k1 and a 26 2 off of k1
4 f5s 12 7 off of 1
And 26 2 off of 1

Gl B. At 1, 3, 5, 7 - f 8 6

Gl m. 3 5. 2 f16s
Gl 1 d e. 2 f16s
Gl 6 d e 2 f 16s

All above footings ok to pour
07/02/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval all spot footings within footprint of building OK