Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2020 | FIRE - ALARM FINAL | Approved | ||
| 04/07/2020 | FIRE - ALARM FINAL | Denied | -Provide copy of Fire Alarm inspection report -Secure control valves on 2nd and 3rd floors |
|
| 01/21/2020 | FIRE - ALARM FINAL | Denied | Still has not provided the FA inspection report. Tamper switch on 2nd floor for control valve shall be monitored. | |
| 12/16/2019 | FIRE - ALARM FINAL | Partial Approval | Provide copy of most recent FA inspection report (waterflow notification system) |