Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2019 | PLUMBING - GAS RECONNECT | Approved | ||
| 05/06/2019 | PLUMBING - GAS RECONNECT | Denied | 1- Shall provide a air pressure test on the system with a 15 lb 1/10 increments test gage with a minimum of 3 lbs of pressure. 2- Shall provide a carbon monoxide detector and locate it in the hallway by furnace 3- Shall provide a mobile home approved gas flex connector at meter connection. |