Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/10/2020 |
FIRE - FINAL |
|
Approved |
Appeal approved for corridor and door |
| 01/15/2020 |
FIRE - FINAL |
|
Denied |
New build out created a corridor which was not addressed by the architect. Needs to be a 1-hr rated corridor. This is in addition to the door violation. |
| 01/09/2020 |
FIRE - FINAL |
|
Denied |
-Need to submit a revised set of plans showing sliding exit door. Horizontal sliding exit door not permitted. IFC 1010.1.2 |