Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM03164
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2021 | FIRE - FINAL | Approved | 1. Had them remove the keyed lock on the west exit door leading out of the back patio fenced in area. Had them add an exit sign over the door. | |
10/20/2020 | FIRE - FINAL | Partial Approval | Partial approval for the south end of the address plus the offices. 1. Still need the north end completed along with the kitchen. 2. Tested tamper and water flow and walked all sprinkler heads within the south end of the address and offices. 2. Fire alarm passed and approved. 3. Need knox box installed on the riser room door. 4. Need the riser room to be labled. 5. Need a sign showing FACP on the Fire alarm door. 6. The Fire alarm has been tested and approved. 7. Need to have keyed lock and thumb turn lock removed from the southwest exit door. 8. Need to have exterior lighing over the exits. Ok for TCO per Tucson Fire. |