Inspection History: FIRE SPKLR - FINAL
Permit Number - T19CM03164
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2021 | FIRE SPKLR - FINAL | Approved | ||
10/20/2020 | FIRE SPKLR - FINAL | Partial Approval | Partial approval for the south end of the address plus the offices. 1. Still need the north end completed along with the kitchen. 2. Tested tamper and water flow and walked all sprinkler heads within the south end of the address and offices. 2. Fire alarm passed and approved. 3. Need knox box installed on the riser room door. 4. Need the riser room to be labled. 5. Need a sign showing FACP on the Fire alarm door. 6. The Fire alarm has been tested and approved. |