Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
Permit Number - T19CM03163
Inspection Description - PLUMBING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2019 | PLUMBING - FINAL | Partial Approval | 1- Building final is recommended for C of O pending air balance and water chlorination report approva | |
09/30/2019 | PLUMBING - FINAL | Approved | REVIEW OF WATER DISINFECTION REPORT COMPLETED | |
09/25/2019 | PLUMBING - FINAL | Denied | 1- Shall provide a water chlorination report prior to Final. 2- Shall provide vacuum relief valve for the water heater. 3- Shall provide a female coupling with plug for the Hand Sink clean out under the case Work. 4- The Hand Sink trap arm shall not have a vertical offset. This will siphon the trap |
|
05/03/2019 | PLUMBING - FINAL | Prior to Final Inspectn | WATER DISINFECTION REPORT REQUIRED |