Permit: T19CM02996

Parcel: 130120880


Addresses:

3757 E ELLINGTON PL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/18/2019 PLUMBING - INTERMEDIATE Approved
07/12/2019 PLUMBING - INTERMEDIATE Partial Approval both pex piping and ABS piping needs to be under water test at time of inspection, also closet ring needs to be installed in front bathroom.
07/08/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Building locked up/no one on site at 12:10pm. No message left, recall and leave message with access instructions.
07/03/2019 PLUMBING - INTERMEDIATE Correction Required Bathroom lavy vent to be 6" above the flood rim of the sink bowl.
Install Closet ring screw to concrete at the toilet.
Fill all plumbing pipes with water VTR for test. Water pipes shall be under working pressure.
PEX is to be secured every 32".