Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2019 | FRAMING | Approved | ||
| 07/12/2019 | FRAMING | Partial Approval | follow details on page 4 on framing ceilings, each individual 2 x 4 is supported by a strut in the middle. Still need correct size T straps at patio per previous correction. | |
| 07/08/2019 | FRAMING | Not ready for Inspection | Building locked up/no one on site at 12:10pm. No message left, recall and leave message with access instructions. | |
| 07/03/2019 | FRAMING | Correction Required | Replace split roof rafter at interior wall of kitchen. Plans do not reflect the ceiling framing done at the entry room at the front door Patio post to beam require a T strap that connects the post to the beam as designed. Anchor bolts required as discussed in the walk through. Finish roof sheathing where old service panel still exists. |
|