Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T19CM02951
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2019 | ELECTRIC - SERVICE UPGRADE | Approved | 1050 E. 19th st. The TEP clearance code is INCR. 1040 E. 19th st. The TEP clearance code is ECO. 910 S. Santa Rita Ave. The TEP clearance code is ECO |
|
08/20/2019 | ELECTRIC - SERVICE UPGRADE | Approved | The TEP clearance code is ECO. | |
08/09/2019 | ELECTRIC - SERVICE UPGRADE | Partial Approval | would prefer to speak with the electrician before turning in a clearance for TEP. Grounds and bonds are not landed. Feeders from meter side do not appear to be torqued. Also question about disconnect locations. |