Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T19CM02940
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2022 | PLUMBING - FINAL | Approved | ||
03/04/2020 | PLUMBING - FINAL | Denied | 1- Shall provide a sediment trap at the water heater. 2- Shall provide a minimum of 5 feet of double wall flu vent and cap for th3 water heater. 3- Shall provide a draft collar for the water heater. 4- Shall provide (3) sheet metal screws per joint and draft collar for the water heater flu vent |
|
02/28/2020 | PLUMBING - FINAL | Denied | Missing smoke and carbon monoxide detectors. |