Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS RECONNECT
Permit Number - T19CM02890
Inspection Description - PLUMBING - GAS RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2019 | PLUMBING - GAS RECONNECT | Approved | ||
| 06/06/2019 | PLUMBING - GAS RECONNECT | Partial Approval | 4502 APPROVED BUT 4504 WAS CANCELED BY CUSTOMER Clearance SWG. Called in to 2:31 PM. |
|
| 06/03/2019 | PLUMBING - GAS RECONNECT | Denied | Flex line may not penetrate furnace cabinet. Hard pipe required. Sediment trap large gas appliances |
|
| 05/28/2019 | PLUMBING - GAS RECONNECT | Denied | Test not holding pressure Electric main panel has arc burns on a main lug and cover. For 4504--Gas not under test. Electric is on in this unit |
|
| 04/24/2019 | PLUMBING - GAS RECONNECT | Not ready for Inspection | Provide air test on gas piping, provide access to all electrical outlets and components, some electrical in disrepair |