Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T19CM02888
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2019 | FIRE - ALARM FINAL | Approved | Approved by CB 9/6/19 | |
07/26/2019 | FIRE - ALARM FINAL | Partial Approval | Only tested smoke and pull station. Notification appliances all worked. Need to test the following by 7/29 or 7/30 in the morning prior to opening. -Need to test duct smokes. These do not need to pass by monday. It may take a while to resolve the issues with these. -Will need a 72 record of completion once finaled. -Need to test water flow and tamper. -Need to verify all signals with central station. -Correct timestamp on panel. -Need waterflow tested and passed by monday or tuesday morning. ok for TCO for full occupancy |