Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2019 | ELECTRIC - RECONNECT | Approved | ||
| 05/03/2019 | ELECTRIC - RECONNECT | Not ready for Inspection | No access. Vacant house fares and sec door locked. Lock box hanging open and no key inside. Recall when ready and have access | |
| 05/02/2019 | ELECTRIC - RECONNECT | Correction Required | Label all circuit breaker functions in the service panel Water Bond; tighten the clamp and GEC bonding screw as it is loose Appears this house does not have natural gas and is all electric Smoke detectors and CO2 detectors are in place |
|
| 04/24/2019 | ELECTRIC - RECONNECT | Denied | 1. A few missing cover plates. 2. Exposed wiring below 7’ in garage and water heater room. 3. No electric disconnect at water heater. 4. Repair/ replace main panel cover. 5. Different gauge ground wires double tapped in main panel. 6. No evidence of main system ground. 7. Install smoke detectors in all bedrooms and a carbon monoxide tester in hallway, all per manufacturers specs. 8. Remove all extension cord wires run through walls. 9. Engage a licensed electrician to further evaluate system and make all necessary repairs. |