Permit: T19CM02885

Parcel: 136336360


Addresses:

9499 E MYRA DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/06/2019 ELECTRIC - RECONNECT Approved
05/03/2019 ELECTRIC - RECONNECT Not ready for Inspection No access. Vacant house fares and sec door locked. Lock box hanging open and no key inside. Recall when ready and have access
05/02/2019 ELECTRIC - RECONNECT Correction Required Label all circuit breaker functions in the service panel
Water Bond; tighten the clamp and GEC bonding screw as it is loose
Appears this house does not have natural gas and is all electric
Smoke detectors and CO2 detectors are in place
04/24/2019 ELECTRIC - RECONNECT Denied 1. A few missing cover plates.
2. Exposed wiring below 7’ in garage and water heater room.
3. No electric disconnect at water heater.
4. Repair/ replace main panel cover.
5. Different gauge ground wires double tapped in main panel.
6. No evidence of main system ground.
7. Install smoke detectors in all bedrooms and a carbon monoxide tester in hallway, all per manufacturers specs.
8. Remove all extension cord wires run through walls.
9. Engage a licensed electrician to further evaluate system and make all necessary repairs.