Permit: T19CM02883

Parcel: 126090290


Addresses:

4150 E OXFORD DR

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/10/2019 PLUMBING - ROUGH, SOIL Approved
05/08/2019 PLUMBING - ROUGH, SOIL Correction Required 1-Bathtub vent is connected before the trap.
2-No test on piping.
3-No tracer wire on exterior piping.
4-Slope of building sewer is not per Code.
5-Quarter bends outside do not have clean outs installed. 6-farthest clean out is not two-way
05/03/2019 PLUMBING - ROUGH, SOIL Not ready for Inspection Too many corrections to write. Advised to get professional help. I went over corrections with owner/builder.