| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2019 | FRAMING | Approved | Ok to mesh, rock and tape. | |
| 07/24/2019 | FRAMING | Not ready for Inspection | Called as requested, left message as no answer. See prior corrections from previous inspector on I Pad. No one home and no plans or revisions found on sit |
|
| 07/11/2019 | FRAMING | Correction Required | 1-Obtain approval of 2035 and 3035 inspections. 2-Ridge beam is 4x10; plans call for 8x10. 3-Bearing wall calls for triple 2x6 header(although a 2x4 wall); double 2x6 is installed. 4-Fire-blocks missing at bearing wall. 5-Gabel wall framing is incomplete. |
|
| 07/09/2019 | FRAMING | Not ready for Inspection | Framing is installed on masonry columns that have not been inspected, and are now grouted. Spoke with Miguel, who will contact office for resolution. |