Permit: T19CM02601

Parcel: 134233210


Addresses:

426 S GRINNELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/09/2019 ELECTRIC - SERVICE UPGRADE Approved Will see labeled breakers at final

TEP Clearance, INCR
05/08/2019 ELECTRIC - SERVICE UPGRADE Correction Required For Clearance the new panel must have 2 Ground Rods a minimum of 6’ apart, Water Bond, Gas Bond, and #4 GEC System based on service entrance cable size in NEC or IRC tables.
TEP does not want cable mast guy wires, they want hard pipe EMT style mast bracing.
Breaker labeling and sub panel wiring can be seen at final.