Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 04/11/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
expose heads of ground rods. Electrical underground from main panel to sub panel was never inspected. Two Conduit’s into subpanel both appear to be overloaded. No more than half an inch sheathing into panel on Romex. Sub panel needs to be labeled. It appears that all work was done hot as there is no inspection history and new panel already hot. Contractor asked for a 30 minute call ahead, voicemail box was full. |