Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T19CM02534
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2019 | ELECTRIC - SERVICE UPGRADE | Approved | ||
04/11/2019 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | expose heads of ground rods. Electrical underground from main panel to sub panel was never inspected. Two Conduit’s into subpanel both appear to be overloaded. No more than half an inch sheathing into panel on Romex. Sub panel needs to be labeled. It appears that all work was done hot as there is no inspection history and new panel already hot. Contractor asked for a 30 minute call ahead, voicemail box was full. |