Permit: T19CM02522

Parcel: 11307243A

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
10/11/2019 PLUMBING - ABOVE CEILING Approved
10/10/2019 PLUMBING - ABOVE CEILING Cancelled IVRS - AP canceled
10/08/2019 PLUMBING - ABOVE CEILING Not Applicable
10/07/2019 PLUMBING - ABOVE CEILING Partial Approval Units 3,4.
10/03/2019 PLUMBING - ABOVE CEILING Denied denied for the 2 east units.
Secure slab flanges.
Correct bearing overbores.
Move pex from cans.
Need dwv and potable.
Repair stapled pex.