Permit: T19CM02373

Parcel: 10709049B


Addresses:

2445 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T19CM02373

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2019 PLUMBING - INTERMEDIATE Approved
04/15/2019 PLUMBING - INTERMEDIATE Denied 1- Shall provide a mission specialty coupling when connection dissimilar material.
2- Shall provide a San Tee for the trap arm to the Floor Sink.
3- Shall seal the waste line penetration thru the exterior wall.
4- Shall caulk the Triple compartment sink.
5- Retest the system.