Permit: T19CM02342

Parcel: 133326060

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/12/2019 PLUMBING - FINAL Approved
04/10/2019 PLUMBING - FINAL Denied Provide minimum 1 inch clearance from B-vent to combustibles, this is the second failed inspection, another failed inspection will result in a re-fee.
04/09/2019 PLUMBING - FINAL Not ready for Inspection Cancel by contractor.
04/04/2019 PLUMBING - FINAL Denied Sediment trap on the wrong side of shut off valve install at regulator valve. Remove shield where B-vent penetrates ceiling , need to verify 1 inch clearance to combustibleā€˜s.