Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2019 |
PLUMBING - FINAL |
|
Approved |
|
| 04/10/2019 |
PLUMBING - FINAL |
|
Denied |
Provide minimum 1 inch clearance from B-vent to combustibles, this is the second failed inspection, another failed inspection will result in a re-fee. |
| 04/09/2019 |
PLUMBING - FINAL |
|
Not ready for Inspection |
Cancel by contractor. |
| 04/04/2019 |
PLUMBING - FINAL |
|
Denied |
Sediment trap on the wrong side of shut off valve install at regulator valve. Remove shield where B-vent penetrates ceiling , need to verify 1 inch clearance to combustibleās. |