Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T19CM02283
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2019 | ELECTRIC - RECONNECT | Approved | OK to clear electric RECN. Also finish installing smoke and carbon alarms that are sitting on the dining room table. One in each bedroom and smoke and carbon outside of sleeping area. | |
04/03/2019 | ELECTRIC - RECONNECT | Not ready for Inspection | 1-Expose grounding electrode conductor and the connection of it to both ground rods. 2--Provide access to inside of house to verify installation of smoke detectors per Code |