Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2019 | ELECTRIC - SERVICE UPGRADE | Approved | INCR OK to clear. | |
| 04/02/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | Need 2 Ground Rods 6’ apart with #4 GEC, Water Bond, and Gas Bond |