Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM02211
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2019 | FIRE - FINAL | Approved | ||
| 08/09/2019 | FIRE - FINAL | Denied | - Two sprinkler heads shall be relocated or fixtures moved. One in kitchen which is less than 3 ft from the center of the fan. The other is less than 4" from a light fixture. - Sprinkler shall be added to the porch areas. Original plans show sprinklers in these areas. NFPA 13 systems require sprinklers. - Extinguishers are outdated shall be inspected and tagged. - Light fixture in riser room shall have a cover. - Signs required: Riser Room, FACP, and FDC. - Knox box shall be required with codes and keys labeled for all doors. - Emergency lighting in two rooms missing, shall put EM lighting in. - Electrical panel shall have schedule in place. |
|
| 08/08/2019 | FIRE - FINAL | Denied | No one on site and doors locked at 12:00pm. |