Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T19CM02211
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2019 | FIRE SPKLR - FINAL | Approved | ||
| 08/09/2019 | FIRE SPKLR - FINAL | Denied | - Two sprinkler heads shall be relocated or fixtures moved. One in kitchen which is less than 3 ft from the center of the fan. The other is less than 4" from a light fixture. - Sprinkler shall be added to the porch areas. Original plans show sprinklers in these areas. NFPA 13 systems require sprinklers. |