Permit: T19CM02202

Parcel: 141094240


Addresses:

6339 E LACO WY

Inspection Status: Passed

Inspection History: COT - LCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
10/04/2019 COT - LCPL - Plumbing Intermediate  DMUNIZ Approved Entered by DMERANZ1 -
10/01/2019 COT - LCPL - Plumbing Intermediate  TVALENCIA Denied Entered by DMERANZ1 - 1- Second Floor Sanitary waste and vent does not set the requirements for horizontal wet venting per Section P3108 2012 IRC 2- Water lines to close to electric can lights 3- Retest the Sanitary system 4- Approved plans call out for the water supply line to the water heater shall be 11/4 inch in size. This is due to the wfu load of the hot water distribution.
09/27/2019 COT - LCPL - Plumbing Intermediate  DMUNIZ Denied Entered by DMERANZ1 - Repair damaged Pex lines (multiple locations). Provide DWV and Potable water test.