Inspection History Details
Inspection Status: Passed
Inspection History: COT - LCBU - Framing
Permit Number - T19CM02202
Inspection Description - COT - LCBU - Framing
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2019 | COT - LCBU - Framing | DMUNIZ | Approved | Entered by DMERANZ1 - |
10/01/2019 | COT - LCBU - Framing | TVALENCIA | Denied | Entered by DMERANZ1 - 1- Second Floor Sanitary waste and vent does not set the requirements for horizontal wet venting per Section P3108 2012 IRC 2- Water lines to close to electric can lights 3- Retest the Sanitary system 4- Approved plans call out for the water supply line to the water heater shall be 11/4 inch in size. This is due to the wfu load of the hot water distribution. |
09/27/2019 | COT - LCBU - Framing | DMUNIZ | Denied | Entered by DMERANZ1 - Fire Block and seal chases, Fire Block Top plate penetrations where needed. Provide anchor bolts at sill plate where needed. |