Permit: T19CM02200

Parcel: 141094230


Addresses:

6347 E LACO WY


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T19CM02200

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/30/2019 PLUMBING - INTERMEDIATE Approved
09/27/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Work incomplete upon arrival.
09/24/2019 PLUMBING - INTERMEDIATE Denied 1- Second Floor water closet does not comply with the horizontal wet venting requirements.
2- Approved plans call for the 1 1/4” cold supply go all the way to the water heater.
3- 3/4 inch water line is crossing the truss gusset plate over the kitchen area.
09/20/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Contractor rescheduled Via phone call