Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2020 |
BUILDING - FINAL |
|
Approved |
|
| 01/06/2020 |
BUILDING - FINAL |
|
Partial Approval |
Relocate two outside air inlets to meet 10 foot distance requirements on RTU’s. Provide shower wand, handle not to exceed 48 inches in height. OK to apply for temporary certificate of occupancy. |
| 01/06/2020 |
BUILDING - FINAL |
|
Partial Approval |
REVIEW OF WATER DISINFECTION REPORT COMPLETED |
| 12/27/2019 |
BUILDING - FINAL |
|
Not ready for Inspection |
Complete all inspections including fire finals. Electrical OK at walls and offices, still need furniture/cubes and restrooms. Complete all plumbing In restrooms, need to complete for ADA. Unable to check mechanical on roof due to weather. |