Permit: T19CM02180

Parcel: 12810076A


Addresses:

350 S WILLIAMS BL


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T19CM02180

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2020 BUILDING - FINAL Approved
01/06/2020 BUILDING - FINAL Partial Approval Relocate two outside air inlets to meet 10 foot distance requirements on RTU’s. Provide shower wand, handle not to exceed 48 inches in height. OK to apply for temporary certificate of occupancy.
01/06/2020 BUILDING - FINAL Partial Approval REVIEW OF WATER DISINFECTION REPORT COMPLETED
12/27/2019 BUILDING - FINAL Not ready for Inspection Complete all inspections including fire finals. Electrical OK at walls and offices, still need furniture/cubes and restrooms. Complete all plumbing In restrooms, need to complete for ADA. Unable to check mechanical on roof due to weather.