Permit: T19CM02179

Parcel: 134251430

Inspection Status: Passed

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
03/25/2020 COT - RSEL - Electrical Final  DMUNIZ Approved Entered by SFLORES2 - Clear TEP DGC
03/05/2020 COT - RSEL - Electrical Final  WGALLAG1 Denied Entered by DMERANZ1 - previous correction not completed, split neutral and ground buss not completed in old service panel RE-INSPECTION FEES apply.
02/21/2020 COT - RSEL - Electrical Final  MRAMBER Denied Entered by DMERANZ1 - No one home. Gate locked, no access. No message. Another failed inspection will result in a reinspection fee
02/07/2020 COT - RSEL - Electrical Final  WGALLAG1 Not ready for Inspection Entered by DMERANZ1 - Please mark all conduits and the existing sub panel per note 3 of your drawings Seal conduit penetration at top of roof jack Existing circuit breaker panel that was made into a sub panel needs to have a split neutral and ground buses