Permit: T19CM02066

Parcel: 120081310


Addresses:

4538 S LIBERTY AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2019 ELECTRIC - FINAL Approved move one bedroom smoke alarm 3 feet away from supply air, still need smoke alarm outside of sleeping area, carbon ok.
03/25/2019 ELECTRIC - FINAL Not ready for Inspection smoke alarms needed in each sleeping area 3 feet away from supply air. Carbon monoxide alarm needed outside of sleeping area. Cover plates needed at exposed receptacles and switches. Kitchen and bathroom circuits and their receptacles are on a three prong system and need to be GFCI protected. 30 amp receptacle in garage is run off an extension cord. Junction box in garage ceiling needs cover plate. Exposed wiring and incorrect wiring done at water heater and back patio. Recommend getting a licensed electrician to make these repairs.