Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM02053
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2020 | FIRE - FINAL | Approved | ||
| 03/18/2020 | FIRE - FINAL | Denied | 1 notification device needs to be replaced as it will cause synchronization issues with the suite per NFPA 71 Building fire alarm is public mode and requires notification in the exam rooms notification devices shall be 80" entire lense per NFPA 72 relocate to proper height Mount Fire Extinguisher Pay re-inspection fee prior to calling fire final back in |