Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/15/2019 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 07/01/2019 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
All roof top duct to have 2 inch liner, provide fire blocking at existing wall, provide bird blocking at new wall, remove blocking at existing opening above ceiling, provide smoke alarms per plan, sheathing not properly nailed, Seal all penetrations through top plating, waste piping not on test, |