Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2019 |
RESIDENTIAL INTERMEDIATE |
|
Approved |
|
| 07/15/2019 |
RESIDENTIAL INTERMEDIATE |
|
Partial Approval |
CHANGE TO PARTIAL FOR PORCH ENCL REVISION INSPECTION |
| 07/01/2019 |
RESIDENTIAL INTERMEDIATE |
|
Not ready for Inspection |
All roof top duct to have 2 inch liner, provide fire blocking at existing wall, provide bird blocking at new wall, remove blocking at existing opening above ceiling, provide smoke alarms per plan, sheathing not properly nailed, Seal all penetrations through top plating, waste piping not on test, |