Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/19/2019 PLUMBING - INTERMEDIATE Approved
07/18/2019 PLUMBING - INTERMEDIATE Not ready for Inspection Too many items to list beyond previous inspection results, walked project with builder,Recall when all issues have been addressed.
07/17/2019 PLUMBING - INTERMEDIATE Denied 1- Plumbing is incomplete.
2- Shall seal the top plate electric conductors penetrations with fire rated foam or caulk.
3- Shall provide (3) sided blocking for all forced air vents.
4- Shall remove the fernco coupling located at the front South East wall and provide a mission specialty coupling.
5- Shall provide a minimum of 12 inches of separation of the water lines to the can lights.